Cooper&Hunter Light Commercial • Universal Floor/Ceiling • R410A • 208–230V
Cooper&Hunter 60,000 BTU Single Zone Universal Floor/Ceiling Minisplit Heat Pump System R410A 230V
System: CH-60LCFC-W + CH-N60LCU-230VO
CLICK HERE TO CONTACT US FOR CUSTOM QUOTES AND QUESTIONS
CLICK TO CALL US 800-543-8933 FOR ANY QUESTIONS
Overview
Universal Floor/Ceiling units are built for flexible placement—install horizontally on a ceiling or vertically on a wall depending on the space. This bundle pairs the CH-60LCFC-W indoor unit with the CH-N60LCU-230VO outdoor condenser for a single-zone R410A heat pump system on 208–230V power.
Control options include the included remote, compatibility with wired controllers (120X/120N), and app control when used with Cooper&Hunter’s optional WiFi kit.
Highlights
Single Zone bundle
Floor or ceiling mount
R410A refrigerant
Indoor SEER2: 19.8
Outdoor SEER2: 17.3
Lines: 3/8" • 7/8"
Outdoor max line: 213.25 ft
Heat down to -22°F ambient
AHRI Ref: 210799609
- Flexible installation: mount on the ceiling (horizontal) or on the wall (vertical).
- Multiple control paths: remote included; supports wired controllers and optional app control with WiFi kit.
- Long-run capable: outdoor platform supports extended line sets and significant elevation changes (see Outdoor Specs).
- Cold-climate capable: outdoor unit supports heating in low ambient conditions down to -22°F.
IndoorCH-60LCFC-W
OutdoorCH-N60LCU-230VO
Cooling55,000 BTU/h (outdoor)
Heat60,000 BTU/h (10,200–62,000)
What’s Included
- Indoor universal floor/ceiling unit: CH-60LCFC-W
- Outdoor condenser: CH-N60LCU-230VO
- Manufacturer documentation (see Documents & Downloads)
- Installation kits are not included unless selected on the Variant Options (No installation, 16ft, 25ft, 50ft).
Indoor Specs
| Spec | Details |
|---|---|
| Model | CH-60LCFC-W |
| System type | Single-zone unit |
| Refrigerant type | R410A |
| BTU rated | 60,000 |
| Power source | 208–230V, 1Ph, 60Hz |
| Voltage range | 187–253 V |
| Dehumidification | 16.00 pints/day |
| EER2 | 9.8 |
| SEER2 | 19.8 |
| Refrigerant piping (liq/gas) | 3/8" / 7/8" |
| Controller | RG10K-exclusive remote & 120X or 120N wire controller compatible |
| Indoor noise (H/M/L) | 54 / 47 / 44 dB(A) |
| Indoor air flow | 1,430 / 1,384.12 / 1,028.82 / 795.29 CFM |
| Operation range (Heating) | 32–86°F (room) |
| Operation range (Cooling) | 62–90°F (room) |
| Minimum circuit ampacity | 3 |
| Max fuse | 15 |
| Unit dimensions (W×H×D) | 64.96 × 26.57 × 9.25 in |
| Packing dimensions (W×D×H) | 67.91 × 29.72 × 12.52 in |
| Net / Gross weight | 96.56 / 111.99 lb |
| Drain pipe diameter | 1" |
Outdoor Specs
| Spec | Details |
|---|---|
| Model | CH-N60LCU-230VO |
| System type | Single-zone unit |
| Refrigerant type | R410A |
| BTU rated | 60,000 |
| Power source | 208–230V, 1Ph, 60Hz |
| Voltage range | 187–253 V |
| Max pipe length | 213.25 ft |
| Max height difference | 98.42 ft |
| Refrigerant piping (liq/gas) | 3/8" / 7/8" |
| Cooling capacity (Min/Max) | 55,000 (20,000–55,000) BTU/h |
| Heating capacity (Min/Max) | 60,000 (10,200–62,000) BTU/h |
| SEER2 | 17.3 |
| EER2 | 9 |
| HSPF2-5 | 8.4 |
| HSPF2-4 | 10.2 |
| COP | 2.98 |
| Outdoor noise level | 61 dB(A) |
| Outdoor air flow | 4,235.29 CFM |
| Minimum circuit ampacity | 44 |
| Max fuse | 60 |
| Ambient temp (Heating) | -22–75°F |
| Ambient temp (Cooling) | 5–122°F |
| Unit dimensions (W×H×D) | 37.48 × 16.34 × 52.48 in |
| Net / Gross weight | 240.74 / 271.61 lb |
| Refrigerant precharge | 25 |
| Additional charge (3/8" liquid) | 0.32 |
Documents & Downloads
- Submittal (PDF) — CH-N60LCU-230VO + CH-60LCFC-W
- Submittal (PDF) — CH-NHPR60LCU-230VO + CH-60LCFC-W
- Universal Floor/Ceiling Booklet (PDF)
- MultiZone Combination (PDF) — HYPER
- MultiZone Combination (PDF) — Regular
- Submittal (PDF) — CH-N60LCU-230VO + CH-60LCDTUI
- Submittal (PDF) — CH-N60LCU-230VO + CH-60AHU
- Submittal (PDF) — CH-N60LCU-230VO + CH-60LCFCI
- AHU Leaflet (PDF)
- User Manual (PDF) — 36–60K AHU
- AHRI Directory Reference — 210799609
Videos
Mini-split installation videos
Products overview
Mini-Splits
Important
- Confirm mounting orientation (ceiling vs wall), clearances, and condensate routing prior to installation.
- Verify line size requirements (3/8" liquid, 7/8" suction) and maximum run/height limits before ordering materials.
- Installation kits are not included unless selected on the Variant Options (No installation, 16ft, 25ft, 50ft).
FAQs
Is this a single-zone system?
Yes—this is a single-zone bundle pairing CH-60LCFC-W with CH-N60LCU-230VO.
Where can the indoor unit be installed?
The universal indoor unit can be installed horizontally on a ceiling or vertically on a wall.
Are installation kits included?
No. Installation kits are only included if selected on the Variant Options (No installation, 16ft, 25ft, 50ft).
Can I use app control?
App control is available when used with Cooper&Hunter’s optional WiFi kit and the C&H app.
How cold can this system heat?
The outdoor unit supports heating in ambient temperatures down to -22°F.